Environmental Considerations

The following table specifies temperature, humidity, and other environmental considerations for safely housing the instrument.

Element

Specification

Temperature

Maintain a server room temperature of 0°C to 35°C. This temperature is the operating temperature of the DRAGEN Server. Do not allow the ambient temperature to vary by more than ±2°C.

Humidity

Maintain a noncondensing relative humidity between 10–85%.

Altitude

Locate the DRAGEN Server at an altitude below 2,000 m (6,500 ft).

Air Quality

Operate the server in a data center environment with air filtration per ISO 14644-1 Class 8 with a 95% upper confidence limit.

Ventilation

Consult your facilities department for ventilation requirements sufficient for the level of heat output expected from the DRAGEN Server.

Location

Operate the server in an indoor environment only. The server is not suitable for use in locations where children are likely to be present. The server is intended for use in a server room.