Laboratory Requirements
Use the specifications and requirements provided in this section to set up the lab space.
Instrument Dimensions
|
Measurement |
Instrument Dimensions |
|---|---|
|
Height |
65 cm (25.6 in) |
|
Width |
40 cm (15.7 in) |
|
Depth |
45 cm (17.7 in) |
|
Weight |
36 kg (79.4 lb) |
Placement Requirements
Position the instrument to allow proper ventilation, access for servicing the instrument, and access to the power switch, power outlet, and power cord.
| • | Position the instrument so that personnel can reach around the right side of the instrument to turn on or turn off the power switch. This switch is on the back panel adjacent to the power cord. |
| • | Position the instrument so that personnel can quickly disconnect the power cord from the outlet. |
| • | Make sure that the instrument is accessible from all sides using the following minimum clearance dimensions. |
| • | Place the UPS on either side of the instrument. The UPS can be placed within the minimum clearance range of the instrument sides. Refer to Uninterruptible Power Supply for more information. |
|
Access |
Minimum Clearance |
|---|---|
|
Sides |
Allow at least 30 cm (12 in) on each side of the instrument. |
|
Rear |
Allow at least 15 cm (6 in) behind the instrument. |
|
Top |
Allow at least 61 cm (24 in) above the instrument. |
Lab Bench Guidelines
Place the instrument on a sturdy and level lab bench away from sources of vibration.
Vibration Guidelines
During sequencing runs, use the following guidelines to minimize vibrations and ensure optimal performance:
| • | Place the instrument on a sturdy lab bench. |
| • | Do not place keyboards, used consumables, or other objects on top of the instrument. |
| • | Install the instrument away from sources of vibration that exceed the ISO Operating Room standard, which is typical for labs. |
For example:
| – | Motors, pumps, shake testers, drop testers, and heavy air flows in the lab. |
| – | Floors directly above or below HVAC fans, controllers, and helipads. |
| – | Construction or repair work on the same floor as the instrument. |
| – | Areas with high foot traffic. |
| • | Keep sources of vibration such as dropped items and movement of heavy equipment at least 100 cm (39.4 in) from the instrument. |
| • | Use only the touch screen, keyboard, and mouse to interact with the instrument. Do not directly impact the instrument surface during operation. |
